‰ NOW 40 WPM ‰ TEXT IS FROM MARCH 2009 QST PAGES 35 AND 81 ‰ OF THE WIRE, INCLUDING THE EXTRA LENGTH, WAS UNZIPPED TO MAKE THE DIPOLE SECTION. AN ELECTRICIANS KNOT SEE FIGURE 1 WAS TIED AT THE JUNCTION OF THE DIPOLE AND THE FEED LINE. AT THE TRANSMITTER END OF THE FEED LINE I UNZIPPED THE WIRE A COUPLE OF INCHES AND ‰ FROM PAGE 81 ‰ KA1CQR 12 B A N2QT 348,968 B B KB8UUZ 33,916 B B ND0C 36,698 B A KW7N 8,704 SEVERAL POINTS. THE LOWEST FREQUENCY WILL BE THE FREQUENCY AT WHICH THE LINE IS A HALF WAVELENGTH, THE NEXT WILL BE TWO HALF WAVELENGTHS, ETC. THE VELOCITY FACTOR CAN THEN BE CALCULATED BY THE RATIO OF THE PHYSICAL LINE LENGTH TO THE VALUE OF A HALF WAVELENGTH IN VACUUM AT THE PARTICULAR FREQUENCY GIVEN BY THE FORMULA L 492/F, WHERE L IS IN FEET AND F IS IN MHZ. THE RESULTS FOR MY ROLL OF NO. 278 1385 SPEAKER WIRE NEAR FOUR AMATEUR BANDS ARE SHOWN IN TABLE 1. SINCE I PLANNED TO BUILD MY ANTENNAS MOSTLY FOR THE 20 METER BAND AND ABOVE, I CHOSE TO USE 0R70 AS THE VELOCITY FACTOR OF THIS LINE. I COULD JUST AS WELL HAVE SAID THAT I PICKED 0R70 BECAUSE IT IS A ROUND NUMBER OR BECAUSE IT IS APPROXIMATELY THE AVERAGE OF THE FOUR READINGS. I THINK THESE RESULTS ARE AMAZINGLY CONSISTENT CONSIDERING THE USE OF A CONSUMER GRADE HANDHELD INSTRUMENT. THERE IS ONLY A 4 VARIATION IN MEASURED VELOCITY FACTOR OVER A FREQUENCY RANGE OF ABOUT AN ORDER OF MAGNITUDE. ATTENUATION THE ATTENUATION OR LINE LOSS WAS ALSO MEASURED ‰ FROM PAGE 81 ‰ 607,005 A C K1DG 1,982,916 A C N5DX 1,389,545 A C KE9I 497,484 A C K5NA 1,249,620 A C K1LZ 1,787,478 A C W4AN 1,029,155 A C VE3XN 245,291 A C W5KFT THE TYPE OF INSULATION USED ON THE RADIOSHACK SPEAKER WIRE ISNT SPECIFIED, BUT I MADE THE ASSUMPTION THAT IT IS POLYETHYLENE OR A SIMILAR MATERIAL THIS SEEMED SAFE SINCE MANY PLASTICS HAVE A SIMILAR DIELECTRIC CONSTANT OF ABOUT 2R3. IN ADDITION, SINCE THE INSULATION BETWEEN THE CONDUCTORS OF THE SPEAKER WIRE IS THICKER PERPENDICULAR TO THE PLANE CONTAINING THE TWO WIRES THAN THE INSULATION FOR 300 TWIN LEAD, IT SEEMED REASONABLE THAT IT MUST HAVE A GREATER INFLUENCE ON THE CHARACTERISTIC IMPEDANCE SINCE MORE OF THE FIELD BETWEEN THE CONDUCTORS WILL PASS THROUGH THE INSULATION AND LESS THROUGH THE AIR. BASED ON ALL OF THIS I ASSUMED THAT THE ADJUSTMENT FACTOR FOR THE CHARACTERISTIC IMPEDANCE WOULD PROBABLY BE CLOSER TO 0R65 THAN TO 0R75, SO THE CHARACTERISTIC IMPEDANCE FOR THIS LINE MIGHT BE Z 224 X 0R65 145R6, OR ABOUT 150. AGAIN, THIS VALUE IS NOT PARTICULARLY IMPORTANT, BUT KEEP IT IN MIND AND WE WILL USE IT LATER TO ESTIMATE LINE LOSS. VELOCITY FACTOR THE VELOCITY FACTOR VF OF THE LINE WAS MEASURED USING THE VA1. THE TECHNIQUE INVOLVES SHORTING THE END OF THE LINE, THEN SWEEPING THE INSTRUMENT OVER A RANGE OF FREQUENCIES TO FIND THE LOWEST IMPEDANCE AT ‰ FROM PAGE 81 ‰ 193,533 A B VE7CC 964,626 A C KA1MDQ 20,800 A B W4KAZ 48,090 A B NR9A 143,226 A B K6XX 943,520 A C K3XO 46,926 A B VE3AT 1,930,480 A C VE4YU 141,030 A B K6AM 648,875 A C VY2ZM 2,339,922 A C VE3EJ 1,923,750 A C N6AN ‰ END OF 40 WPM TEXT ‰ QST DE W1AW ƒ